B513 Planning Meeting, 26th October 2001

Present:          Tony Cass, Marc Collignon, Anne Funken, Jukka Lindroos, Dave Underhill, Tim Whibley

1.             Previous Minutes

·         Denis Raffourt had provided the following quotes for smoke detection systems:

a.       48,600CHF for three ceiling mounted VESDA detectors (one per zone)

b.      36,600CHF for six detectors to be mounted by the air conditioning units

c.       25,560CHF for underfloor detectors

d.      9,480CHF for additional “standard” detectors for the reworked MG room area.

These prices are very similar to those quoted for B613 (e.g. ~30KCHF for two VESDA systems).

·         The implications of motorised circuit breakers on all output feeders are not yet fully understood, but those present from IT favoured being able to power on each row of racks independently. In addition to the space requirements for the PDUs, we also need a better understanding of the control system.

2.             Review of Proposed Floor Plan

·         Anne commented again that 240kW is the maximum additional power available for equipment in the machine and vault until the new substation is in place.

3.             HVAC imposed height restrictions

·         Jukka pointed out that the smoke extraction duct would reduce clearance

a.       to 2.2m in the machine room area by the ramp from the lift and

b.      to 2.06m in the storage rooms along the vault wall, and this for a distance of 1m from the wall.

4.             Substation Planning